Question:

Two years ago I purchased a 25 year old home . The hydro panel is a 200 amp service . Our micro wave quit working (blowing internal breaker). We replaced it . It started tripping breakers. We returned it and replaced it. The booklet of instructions said a 20 amp dedicated line . I installed it . # 12 wire and 20 amp fuse . Still trips the breaker . I move the fuse around to several other locations in the box . Still trips breaker . I have a 60 amp service running to my shop so I tried it out there . No tripping breakers . Even works fine on 15 amp . Any ideas as to why ?

Answer:

This appears to have nothing to do with the oven and everything to do with either the plug, the way the breaker is installed in the panel or the cable leading power to the oven. I'd first replace the plug and then start tracing with a meter.


In the interests of retaining credibility and in fairness to all, I cannot recommend prices, people nor companies for various projects. Courtesy of Ren Molnar, Construction Consultant at HomeFocus.com. I can also be reached at (613) 748-3003 and Home Focus – The Radio Show is broadcast live 8 to 10 A.M. (Ottawa, Ont. time) on Saturdays on www.cfra.com.

Remember, even if you don’t do your own work around the house have to hire someone, you put yourself at a great advantage when you can intelligently discuss a project with the various trades people.

"Ren’s Ren-O-Vations Tips"
is a monthly journal that talks everything to do with HOME OWNERSHIP & MAINTANENCE.

It is sent out in time to have it in your mailbox or on your computer by the 20th of the month – every month.

To order, simply send a cheque or money order to:
Ren,
P.O. Box 9411,
Ottawa, Ontario,
K1G 3V1

E-mail – 12 issues (1 yr.) $17.95.
Regular mail – 12 issues (1 yr.) $33.95.
(subject to change without notice)
Credit card companies take a cut from payments so we are not credit card friendly - can't justify it.
Ren’s Ren-O-Vations Tips
makes the perfect gift any time for almost everyone:
Be My Valentine, Easter, Christmas, Mothers’ Day, Fathers' Day, Birthday, Wedding, Congratulations New Home Owner(s), Thinking Of you,
Good neighbour
Ren

Answered By: Ren Molnar

More Questions & Answers ...

1. I just recently got a ceiling fan installed by an electrician. Part of the reason I hired a professional was ...
2. I am trying to install a new light fixture outlet (and fixture) into an existing circuit, between an existing ...
3. Two years ago I purchased a 25 year old home . The hydro panel is a 200 amp service . Our micro wave quit work ...
4. i am looking to replace a electric water heater in my home. I also want to move it from its current position ...
5. This past weekend I installed the basement humidity reduction fan and duct work as you suggested. I have it s ...
6. I heard somewhere that it is possible to put a timer on your hot water tank. Is this a possibility and if so, ...
7. I own a 17 year old bungalow in the country. We have a bathroom and a washing machine in the basement which t ...
8. Well, I managed to change the belt on my dryer, but need to know how to rewire the door switch properly. Which ...
9. Based on both Canadian and American government reports and on my own personal observations in Europe, tankless ...
10. Based on both Canadian and American government reports and on my own personal observations in Europe, tankless ...
11. Based on both Canadian and American government reports and on my own personal observations in Europe, tankless ...
12. Based on both Canadian and American government reports and on my own personal observations in Europe, tankless ...
13. A friend gave us his 4yr old dishwasher. His complaint about it was that it was to noisy. It works well and t ...
14. I have been runing out of hot water quickly have flushed the tank with the same problem still there .I have h ...
15. We are looking for someone who can be on retainer basis to visit the house- it is townhome in centrepoint area ...
16. If I have remodeling done in my home and the contract says "rough wiring or rough plumbing" what would this in ...
17. When I removed the strip lighting bar I discovered that there is no junction box in the wall. The wires are m ...
18. I want to sell 2 appliances that are 220 voltage: a washer/dryer unit and a gas stove. If someone were to pur ...
19. Last week I replaced a wall switch in a bedroom . At the same time I changed 2 out 3 wall outlets in the same ...
20. I have a 16 cup percolator. It needs a new thermostat. Can you advise me where I can get it repaired? ...
21. A few weeks ago, a lady called with a problem of smelly hot water. Unfortunately, we forgot your solution and ...
22. It is called a European bungalow, and it is heated electrically with wall units. It is about 750 feet, and a ...
23. My ductwork is all metal and all joints are sealed properly. I would like your opinion about shortening the dr ...
24. Our current doorbell has just 'burned out' and we're looking to replace it. I'd like to buy a wireless doorbel ...
25. I have noticed that my dryer vent has balls of lint that are blown out. Also, during the hot summer days, some ...
26. I have a 3 year old raised ranch home and when I turn the heat on in the winter the farthest rooms in the hous ...
27. I can detect a strong draft behind the light fixtures and the thermostat control for the furnace on particular ...
28. I recently replaced a 2-bulb ceiling track light in one bedroom with the newer circular "flush-mounted" type, ...

Home Plans